Water System No. : IL0390050 Federal Type : C
Water System Name : CLINTON State Type : C
Principal County Served : DE WITT Primary Source : GW
Status : A Activity Date : 01-01-1970
Lab Sample No. : SI21046-01_01 Collection Date : 09-21-2012
This list displays sample/results of all non-microbial analytes (TSAANLYT.TYPE_CODE <> MOR) associated to the selected sample. Results for Microbial Analytes are not included.

Analyte Code Analyte Name Method Code Less than Indicator Level Type Reporting Level Concentration level Monitoring Period Begin Date Monitoring Period End Date
1005 ARSENIC 200.8 N 3.880  UG/L 07-01-2012 09-30-2012
1010 BARIUM 200.8 N 7.740  UG/L 01-01-2011 12-31-2013
1015 CADMIUM 200.8 Y MRL 3 UG/L   01-01-2011 12-31-2013
1020 CHROMIUM 200.8 Y MRL 5 UG/L   01-01-2011 12-31-2013
1032 MANGANESE 200.8 Y MRL 15 UG/L   01-01-2011 12-31-2013
1036 NICKEL 200.8 Y MRL 25 UG/L   01-01-2011 12-31-2013
1045 SELENIUM 200.8 Y MRL 2 UG/L   01-01-2011 12-31-2013
1074 ANTIMONY, TOTAL 200.8 Y MRL 2 UG/L   01-01-2011 12-31-2013
1075 BERYLLIUM, TOTAL 200.8 Y MRL 1 UG/L   01-01-2011 12-31-2013
1085 THALLIUM, TOTAL 200.8 Y MRL 2 UG/L   01-01-2011 12-31-2013
1095 ZINC 200.8 Y MRL 100 UG/L   01-01-2011 12-31-2013

 

 


Total Number of Records Fetched = 11