Drinking Water Branch

 

Return Links

 
 Chem/Rad Samples

   Analyte List

 
 Water System Detail

 
 Water Systems

 
 Water System Search

   County Map

Glossary

 

Chem/Rad Sample Results

Water System No. : IL1970450 Federal Type : C
Water System Name : JOLIET State Type : C
Principal County Served : WILL Primary Source : GW
Status : A Activity Date : 01-01-1970
Lab Sample No. : 237085 Collection Date : 02-03-2012
This list displays sample/results of all non-microbial analytes (TSAANLYT.TYPE_CODE <> MOR) associated to the selected sample. Results for Microbial Analytes are not included.

Analyte Code Analyte Name Method Code Less than Indicator Level Type Reporting Level Concentration level Monitoring Period Begin Date Monitoring Period End Date
1002 ALUMINUM 200.7 N MRL 47  UG/L
1005 ARSENIC 200.8 Y MRL 0.95 UG/L  
1010 BARIUM 200.7 N MRL 38.9  UG/L
1016 CALCIUM 200.7 N MRL 28.7  MG/L
1020 CHROMIUM 200.7 Y MRL 5.8 UG/L  
1022 COPPER, FREE 200.7 N MRL 79.8  UG/L
1028 IRON 200.7 N MRL 0.728  MG/L
1031 MAGNESIUM 200.7 N MRL 13.2  MG/L
1032 MANGANESE 200.7 N MRL 112  UG/L
1036 NICKEL 200.7 Y MRL 43 UG/L  
1042 POTASSIUM 200.7 N MRL 15.3  MG/L
1051 STRONTIUM 200.7 N 1000  UG/L
1052 SODIUM 200.7 N MRL 168  MG/L
1075 BERYLLIUM, TOTAL 200.7 Y MRL 0.55 UG/L  
1079 BORON, TOTAL 200.7 N MRL 963  UG/L
1081 COBALT, TOTAL 200.7 Y MRL 13 UG/L  
1083 LITHIUM, TOTAL null Y MRL 110 UG/L  
1084 MOLYBDENUM, TOTAL 200.7 Y MRL 22 UG/L  
1086 TIN, TOTAL null Y MRL 86 UG/L  
1087 TITANIUM, TOTAL null N MRL 0 UG/L 1.98  UG/L
1088 VANADIUM, TOTAL 200.7 Y MRL 47 UG/L  
1095 ZINC 200.7 N MRL 154  UG/L

 

 


Total Number of Records Fetched = 22